Control Valve Sizing

Cv / Kv for liquid, gas/vapour and steam service · ANSI/ISA-75.01.01-2012 · IEC 60534-2-1 · validated <0.5% vs the standard worked examples (methodology).

Edition: ANSI/ISA-75.01.01-2012 · IEC 60534-2-1
Required Cv
190.76
Kv 165· 76% open
FAIL
Sub-critical: service ΔP is below the choked limit.σ=1.33 — likely damaging cavitation; review trim/Δp staging.Required opening 76% within the 20–80% band.
relRho0.9664
dP_kPa460
FF0.9442
dpChoked_kPa497.19
dpSizing_kPa460
sigma1.326
FP1
FLP0.9
FR1
Rev3012128
control-valve-liquid · 1.0.0cv→ANSI/ISA-75.01.01 §7.2 / Eq.1–5 (incompressible) · ff→ANSI/ISA-75.01.01 §7.3 FF critical pressure ratio · dpChoked→IEC 60534-2-1 choked liquid flow · sigma→ISA-RP75.23 cavitation index σ
Multi-case (what-if) · turndown 2.6×
CaseRequired CvOpening
Min95.37838.2%
Normal190.7676.3%
Max247.9899.2%
Inherent characteristic
0% travel100%