Control Valve Sizing
Cv/Kv · liquid/gas/steam · ISA-75.01.01
Open →
DP Flow Elements
orifice · nozzle · venturi · ISO 5167
Open →
Restriction Orifice
single & multi-stage · choke + cavitation
Open →
Engine contract self-test — control-valve liquid
190.76Cv · Kv 165
Sub-critical: service ΔP is below the choked limit.σ=1.33 — likely damaging cavitation; review trim/Δp staging.Required opening 95% outside the 20–80% band — review valve size.
relRho0.9664
dP_kPa460
FF0.9442
dpChoked_kPa497.19
dpSizing_kPa460
sigma1.326
FP1
FLP0.9
FR1
Rev2966953